|
|
Surge protective devices are standard on most specifications for industrial and commercial facilities. Specification Criteria For Distribution Surge Protection A specification should focus on the essential performance, installation and safety requirements. But what criteria are important when specifying a surge protection device? The following are considered essential performance, safety, and installation criteria for a specification: Surge Current Per Phase Cutler-Hammer recommends 250 kA per phase for service entrance, 120 kA per phase for panelboards or other locations. Let Through Voltage Performance should be specified based on the three standard IEEE test waveforms (IEEE C62.41 Category C3 and B3 combination waves, and B3 ringwave). Specify the required ratings for applicable nominal voltages on LG and L-N modes. Effective Filter Based on the MIL-STD-220 insertion loss test, noise attenuation at 100 KHz should exceed 50 dB (L-N modes). Specify that test results (bode plots) are provided as submittals. Integrated Installation The SPD should be factory-installed as part of the distribution equipment. Ensure the installation minimizes lead length. Internal Fusing For safety and overcurrent protection, a 200 kAIC internal fusing system should be provided. Reliable Monitoring and Diagnostics This should include foolproof status indication for each phase. A popular option is to include Form C contacts for remote monitoring. Independent Testing To ensure a reliable construction and design, specify that all manufacturers submit results from an independent test lab, verifying the device can achieve the published surge current ratings (on a per mode and per phase basis). To help you understand the importance of these criteria, let’s answer a few commonly asked specification criteria questions. What is Surge Current Capacity? Surge Current Capacity is defined by NEMA LS-1 as the maximum 8/20 us surge current pulse the SPD device is capable of surviving on a single impulse basis, without suffering either performance or degradation of more than ten percent (10%) deviation of clamping voltage . Industry standards publish surge current per-phase, by summing modes L-N and L-G in a Wye system, or L-L and L-G in a Delta system. Surge current capacity is used to indicate the protective capability of a particular SPD design, and should be used on a per-phase and per-mode basis when specifying a SPD for a given application. What Surge Current Capacity is Required? Surge current capacity is dependent on the application and the amount of required protection. The facility’s geographic location and exposure to transients should be considered. Also, consider how critical the equipment is to the facility in terms of downtime and repair costs. Based on available research, the maximum amplitude of a lightning-related surge on a facility’s service entrance is a 20 kV, 10 kA combination wave (refer to IEEE C62.41). Above this amount, the voltage will exceed Basic Insulation Level (BIL) ratings, causing arcing in the conductors and/or the distribution system. Cutler Hammer recommends 250 kA per phase for service entrance applications (large facilities in high exposure locations), and 120 kA per phase at branch panel locations. If the maximum surge is 10 kA, why do many suppliers suggest installing a device that can handle up to 250 kA per phase? The answer is life expectancy . A service entrance suppressor will experience thousands of surges of various magnitudes. Based on statistical data, a properly constructed suppressor with a 250 kA per phase surge current rating will have a life expectancy in excess of 25 years in a high-exposure location. Some manufacturers recommend installing SPDs with surge current ratings of up to 600 or 1000 kA per phase. This level of capacity offers no benefits to the customers. A 400 kA/phase device would have approximately 500-year life expectancy for medium exposure location – well beyond reasonable design parameters. Today's SPDs will not fail due to lightning surges. Based on two decades of experience, the failure rate of an SPD is extremely low; below 0.1%. Should a suppressor fail, it is likely the result of excessive over voltage (swell), due to a fault on the utility power line (i.e., the nominal 120 VAC line exceeds 180 VAC for many cycles). A severe swell will damage surge protectors and other electronic loads, such as computers. Should this rare event occur, call the utility to investigate the problem. Why Shouldn’t Joule Ratings Be Used to Compare SPDs? Joule ratings are not an approved specification for surge protective devices. IEEE, IEC, and NEMA do not recommend using Joule ratings when specifying or comparing surge suppressors because they can provide misleading and conflicting information . For example, on a 120 Volt system, a 150 Volt or 175 Volt MOV could be used. Even though the 175 Volt MOV has a higher Joule rating, the 150 Volt has a much lower let through voltage. Joule ratings are a function of let through voltage, surge current, and surge duration. Each manufacturer may use a different standard surge wave when publishing Joule ratings. For this reason the power quality industry does not recommend the use of Joule ratings in performance specifications. Why is Independent Testing Important? Manufacturers are not required to have their units independently tested to their published surge current capacity rating. Most published ratings are theoretical. They are calculated by summing the individual MOV capabilities. For example, a manufacturer may claim a rating of 100 kA, but due to the poor construction integrity, the unit may be unable to share current equally to each MOV. Without equal current sharing, the expected life expectancy cannot be met. Specifiers should request that manufacturers submit independent test reports from lightning labs confirming the published surge ratings. What is Let-Through Voltage? Let-through voltage (or Clamping Voltage) is the amount of voltage that is not suppressed by the SPD and passes through to the load. Let-through voltage is a performance measurement of a surge suppressor's ability to attenuate a defined surge. IEEE C62.41 has specified test waveforms for service entrance and branch locations. A surge manufacturer should be able to provide let through voltage tests under the key waveforms. Lower let-through voltage offers better surge protection for downstream loads.
Figure 17. Example of SPD Integrated in a Panelboard What Effect Does Installation Have on SPD Performance? Installation is the most important factor in determining the effectiveness of a particular SPD. Installation lead length (wiring) reduces the performance of any surge suppressor. As a rule of thumb, each inch of installation lead length adds between 15 to 25 Volts to the let-through voltage. Because surges occur at high frequencies (approximately 100 kHz), the leads from the bus bar to the suppression element creates impedance in the surge path . Published let-through voltage ratings cover the device or module only. These ratings do not include installation lead length, which is dependent on the electrician installing the unit. Therefore, the actual let through voltage for the system is measured at the bus bar and is based on two factors:
|