Location
Is the distance between the motor and the AF drive a problem? Check in the product catalog. An output filter may be necessary.
Cost
Customers want the least expensive product that will meet all the application’s requirements. As you explain the cost of a particular unit, be sure to put it in terms of the total cost to the customer. What may seem like a high initial cost may in fact save the customer a lot of money over the life of the unit. Energy cost savings, reduced downtime because of on-board diagnostics, and the like can be presented as returns on the investment in the device.
Application Checklist
Here is a good checklist to use when helping a customer decide which type of AF Drive is best for the application.
MOTOR
New ____ Existing ___ Hp ____ Base Speed _____ Voltage _____
FLA ____ LRA ___ NEMA Design ____ Gearbox/Pulley Ratio _____
Hz _____ Service Factor _____
LOAD
Application: ________________________________________________________
Load Type: Constant Torque _____ Variable Torque ____Constant HP _____
Load inertia reflected to motor: _____________ lb.ft2
Required breakaway torque from motor: ___________ ft.-lb.
Running load on motor: ___________ ft.-lb.
Peak torque (above 100% running): __________ ft.-lb.
Shortest/Longest accel time: ____ / ____ sec. up to ____ Hz from stop
Shortest/Longest decel time: ____ / ____ sec. down to ____ Hz from max. speed
Operating speed range: ______ Hz to _____ Hz
Time for motor/load to coast to stop: _____ seconds.
AF DRIVE
Source of start/stop commands: I/O terminals ____ Keypad ____ Other ______
Source of speed adjustment: ________________________________
Other operating requirements: _______________________________
Will the motor ever be spinning when the AF Drive is started? Yes___ No ____
How far apart are the motor and the AF Drive? _________ feet
Is the load considered high-inertia? Yes___ No ____
Is the load considered hard to start? Yes___ No ____
Options desired: Multiple operators ______ Output Signals ______
Power Options _________________________________
Other ________________________________________
Other requirements or conditions: ________________________
POWER SUPPLY
Supply transformer: _____ KVA, or short circuit current at drive input _____ amps
Total Horsepower of all drives connected to supply transformer/feeder ______ Hp
Is a drive transformer or line reactor desired? (May be required) ________
Any harmonic requirements? Y/N % Voltage THD ____% Current THD ____
Total non-drive load connected to the drive’s feeder: ________ amps
SERVICE
Start-Up Assistance: ____________ Customer Training:__________
Preventive Maintenance: _________ Spare Parts: ________
ADDITIONAL ISSUES – Answer Yes or No
____ Will the AF Drive operate multiple motors?
____ Will the power supply source ever be switched with the AF Drive running?
____ Is starting or stopping time critical?
____ Are there any peak torques or impact loads?
____ Will user-supplied contactors be used on the input or output of the AF Drive?
Recommending a Product to the Customer
Using all the information gathered here, consult your product catalogs to make a recommendation to the customer.
It is possible that you may have to suggest more than one product, as you may not find a perfect match for all the application’s requirements.

The centrifugal pump on a chilled water system, shown here, is an ideal candidate for use with an adjustable frequency drive.
As the pump turns faster, it moves more water, and it requires more torque.
This application also requires water flow through the pump to be regulated.
You will need to work with the customer to select an adjustable frequency drive for an application such as this, taking into consideration the factors mentioned above.