As a Service Entrance
As a means of disconnection and fault protection for a motor circuit
Let’s take a moment to consider each purpose briefly.
Service Entrance
A service entrance is a point at which electricity first enters a building.
There are times when a safety switch is used at the service entrance point to disconnect power to the whole building at one location. Consider an existing commercial building. If additional electrical service is required as a result of building expansion, an electrical contractor will usually install safety switches.
Figure 4. Adding Circuits to an Existing Commercial Building
Means of Disconnection
The National Electrical Code® (NEC) requires that a “disconnecting means shall be located in sight from the motor location and the driven machinery location” (Article 430-102b). The NEC defines “in sight” as visible and not more than 50 feet (15.24 meters) from the motor or machinery.
With the power removed, the operator can safely work on the machinery. There is no need to worry about touching live electrical components, or having the motor accidentally start.
Figure 5. Safety Switch Used as Power Disconnection Means
Circuit Protection
Why do we need circuit protection? Circuit protection prevents damage that would otherwise be caused by
Overload (or Overcurrent) and
Short Circuits.
Overcurrent protection devices such as fuses and circuit breakers are used for this purpose.
An overcurrent occurs when too many devices are operated on a single circuit, or a piece of electrical equipment is made to work harder than designed. For example, a motor rated for 10 amps may draw 20, 30 or more amps in an overload condition.

A package has become jammed on this conveyor, causing the motor to work harder and draw more current.
Overloaded Motor
Damage will occur to the motor in a short time unless the problem is corrected or the overcurrent protection device shuts down the circuit. Of course, motors are not the only devices that require circuit protection for an overcurrent. Every circuit requires some form of protection against overcurrent.

Heat is a major cause of insulation failure on any electrical component. Insulated wire exposed to high levels of heat suffers insulation breakdown, and it may even flake off, exposing the conductors.
Figure 6. Insulation and Heat
When two bare conductors touch, a short circuit occurs and resistance drops to almost zero. Short circuit current can be thousands of times higher than normal operating current.
Figure 7. Short Circuit
Ohm's Law gives us the relationship between current, voltage, and resistance. Consider a 240-volt motor with 24 ohms of resistance. It would normally draw 10 amps of current.
I = E / R
I = 240 volts / 24 ohms
I = 10 amps
If a short circuit occurs, the resistance drops. Suppose the resistance drops to 24 milliohms, which is a reasonable figure. This means that the current will rise to 10,000 amps.
I = E / R
I = 240 volts / 0.024 ohms
I = 10,000 amps
The heat generated by this high current will cause extensive damage to connected equipment and conductors.
For this reason, when a short circuit occurs, this dangerous current must be interrupted immediately.